UVPURE Water Steriliser

Technical Specifications
The UVPURE units are available in a number of standard models. There is only one inlet and outlet piping connection required for each model and equal flows are directed to each module.


Electrical supply required is standard 220V, 50 Hz ac. All models are rated at 7 bar operating pressure. The life of the lamps is 8000 hours and hour meters are included as standard equipment. There is an option of a lamp failure alarm with audio and visual indication.
On the left is a schematic diagram of the P-450-DS. It has a 2x3 layout (6 lamps, horizontal x vertical).

 

The electric control box for model P-150-DS
A single-lamp installation
 
 Standard Models: Specifications
Model
Flow Capacities
No. of
Lamps
Lamp
Type
Total
Power
Inlet/
Outlet
Dimensions
L x W x H
Layout
litres/min
m3/hr
Watts
inches/mm
mm
P-015-DS
10
0.6
1
AUV 15
15
3/4" BSP
470X150X260
1x1
P-030-DS
26
1.6
1
AUV 30
30
3/4" BSP
930X150X260
1x1
P-055-DS
43
2.6
1
AUV 55
55
1" BSP
930X150X260
1x1
P-075-DS
63
3.8
1
AUV 75
75
1" BSP
1230X150X260
1x1
P-110-DS
88
5.3
2
AUV 55
110
1 1/4" BSP
930x150x545
2x1
P-150-DS
126
7.6
2
AUV 75
150
1 1/4" BSP
1230x150x570
2x1
P-225-DS
183
11
3
AUV 75
225
1 1/4" BSP
1240x665x575
2x2
P-300-DS
250
15
4
AUV 75
300
2"/63
1240x685x600
2x2
P-450-DS
366
22
6
AUV 75
450
2 1/2"/75
1265x710x965
2x3
P-600-DS
500
30
8
AUV 75
600
3"/90
1295x710x1100
2x4
P-750-DS
633
38
10
AUV 75
750
4"/110
1335x735x1265
2x5
P-900-DS
750
45
12
AUV 75
900
4"/110
1335x735x1400
2x6

*Flow capacities dependent on UV transmission of the water.
*Flow capacities given at a UV dose of 30 mJ/cm2 and UV transmission, T10, of 80%